LAUDA WK class

Circulation chillers with closed cooler circuit for continuous nonstop work in research, technology and production at temperatures from -30 up to 40 °C.

WK class

LAUDA WK class circulation chillers are used where operating heat has to be discharged reliably and quickly in chemical production processes or from technical systems – in harsh constant use environments. Unlike cooling with tap water, they provide a constant temperature irrespective of the time of year and pressure fluctuations. The water saving also protects the environment and significantly reduces operating costs.

Application examples

  • Analytical devices such as electron microscopes, X-ray units, refractometers, distilling systems or AAS units
  • Rotary evaporators and Soxhlet systems
  • X-ray control systems e.g. at airports and semiconductor systems
  • Control of cooling traps e.g. in the drying of gases
  • Central cooling water supplies for complete laboratories to replace cooling with tap water


LAUDA WK class brochureDownload a PDF
of our WK class brochure:

LAUDA WK class Brochure (1 MB)

  The WK class advantages Your benefits
  • 37 different models
  • Cooling capacity from 230 W to 13 kW
  • Independent cooling-water system instead of central cooling-water supply
  • The right solution for all requirements
  • Cooling-water temperature and pressure always constant
  • Avoids the leakage of substances that are hazardous to the environment
  • LED display and 3-button operation
  • Easy operation
  • Easily visible level display and discharge pressure display from WK 1200
  • All devices with submersible pump
  • Important operating parameters visible at a glance
  • No seal problems at the pump shaft
  • Below the bench height of 79 cm on units up to WK 2400
  • Small footprint
  • Fits under the standard laboratory bench top
  • Saves valuable laboratory space

WK class WK circulation chillers up to 600 W

The circulation chillers of the WK class are available with different cooling and pump configurations. The temperature range for all the units is from 0 up to 40 °C.

The LAUDA WK 300 was especially designed for simple cooling tasks down to 0 °C and is ideally suited for the use on the laboratory bench due to its compact size. The circulation chillers WK 500 and WK 502 differ in their cooling and pump output. The WK 502 was especially designed for the connection to atomic absorption spectrometers (ASS). Unlike the WK 500, it has an appropriately upgraded cooling unit and pump.

WK class WK circulation chillers up to 2.8 kW

The differences between the individual units are the effective cooling and pump outputs and the dimensions. All units can be supplied with water cooling (W). This enables greater cooling performance without heating of the surrounding laboratory environment.

WK class WK circulation chillers up to 13 kW

The different cooling capacities are critical when selecting a unit. The WK class circulation chillers from 1 kW cooling capacity upwards are also available with water-cooling (W). In the more powerful WK 7000 to WK 10000 W circulation chillers, a second pump provides the internal circulation in addition to the pump for the external circuit. Thus the cooling capacity and temperature stability do not depend on the flow characteristics in the external circuit. These units can be supplied on request with water cooling (W). For these units, the use of water/glycol mixtures as heat transfer liquid is compulsory.

The LAUDA WK circulation chillers are available with different options, e.g. RS 232/485 interface and enhanced pumping systems.

WK class WKL circulation chillers up to 1 kW

The WKL 230 circulation chiller was especially designed for simple thermostating tasks below 0 °C. Thanks to its extremely compact construction and small footprint it fits anywhere. The temperature range of the WKL 230 is from -10 °C up to 40 °C with a temperature stability of ±0.5 K. The compact circulation chillers WKL 600 to WKL 1000 have different pumps and cooling performance.

WK class WKL circulation chillers up to 13 kW

The WKL circulation chillers differ in terms of their cooling capacities and achieve temperatures of -10 °C (WKL 1200 to WKL 4600 W) or -30 °C (WKL 7000 to WKL 10000 W). All units are also available in the watercooled design (W). With these units, the use of water/glycol mixtures as the heat transfer liquid is compulsory.

Select up to 3 products to compare: Compare Products

WK class WK circulation chillers up to 600 W

Technical features WK 300 WK 500 WK 502
Select to compare:  
Working temperature range* °C 0...40 0...40 0...40
Temperature stability ±K 0.5 0.5 0.5
Cooling output at 20 °C kW 0.31 0.50 0.60
Pump pressure max. bar 0.15 1.0 2.2
Pump flow max. L/min 8 30 33
Cat. No 100 V; 50 Hz/115 V; 60 Hz LWM 717 LWG 732
Cat. No 230 V; 60 Hz LWG 232 LWG 240
 

Summary

Summary

Summary

* Working temperature range is equal to ACC range



WK class WK circulation chillers up to 2.8 kW

Technical features WK 1200 WK 1200 W WK 1400 WK 1400 W
Select to compare:  
Working temperature range* °C 0...40 0...40 0...40 0...40
Temperature stability ±K 0.5 0.5 0.5 0.5
Cooling output at 20 °C kW 1.2 1.5 1.4 1.7
Pump pressure max. bar 3.2 3.2 1 1
Pump flow max. L/min 40 40 30 30
Cat. No. 100 V; 50 Hz/115 V; 60 Hz LWG 733 LWG 761 LWG 737 LWG 762
 

Summary

Summary

Summary

Summary


Technical features WK 2200 WK 2200 W WK 2400 WK 2400 W
Select to compare:  
Working temperature range* °C 0...40 0...40 0...40 0...40
Temperature stability ±K 1 1 1 1
Cooling output at 20 °C kW 2.2 2.6 2.4 2.8
Pump pressure max. bar 3.2 3.2 1 1
Pump flow max. L/min 40 40 30 30
Cat. No. 100 V; 50 Hz/115 V; 60 Hz LWG 734 LWG 763 LWG 738 LWG 764
 

Summary

Summary

Summary

Summary

* Working temperature range is equal to ACC range



WK class WK circulation chillers up to 13 kW

Technical features WK 3200 WK 3200 W WK 4600 WK 4600 W
Select to compare:  
Working temperature range* °C 0...40 0...40 0...40 0...40
Temperature stability ±K 1 1 0.5 0.5
Cooling output at 20 °C kW 3.5 4.0 4.6 5.3
Pump pressure max. bar 3.2 3.2 3.2 3.2
Pump flow max. L/min 40 40 40 40
Cat. No. 208-230 V; 3/PE; 60 Hz LWG 765** LWG 336 LWG 758
Cat. No. 440-480 V; 3/PE; 60 Hz LWG 636
Cat. No. 230 V; 3/PE; 60 Hz LWG 135 LWG 165 LWG 158
 

Summary

Summary

Summary

Summary


Technical features WK 7000 WK 7000 W WK 10000 WK 10000 W
Select to compare:  
Working temperature range* °C 0...40 0...40 0...40 0...40
Temperature stability ±K 0.5 0.5 0.5 0.5
Cooling output at 20 °C kW 7.0 8.5 10.0 13.0
Pump pressure max. bar 3.2 3.2 3.2 3.2
Pump flow max. L/min 40 40 40 40
Cat. No. 208 V; 3/PE; 60 Hz LWG 345 LWG 347
Cat. No. 440-480 V; 3/PE; 60 Hz LWG 645 LWG 647 LWG 649 LWG 651
 

Summary

Summary

Summary

Summary

* Working temperature range is equal to ACC range
** 208 V; 3/PE; 60 Hz



WK class WKL circulation chillers up to 1 kW

Technical features WKL 230 WKL 600 WKL 603
Select to compare:  
Working temperature range* °C -10...40 -25...40 -20...40
Temperature stability ±K 0.5 1.0 1.0
Cooling output at 20 °C kW 0.23 0.65 0.52
Pump pressure max. bar 0.15 1.0 3.2
Pump flow max. L/min 8 30 33
Cat. No. 100 V; 50 Hz/115 V; 60 Hz LWM 716 LWG 741 LWG 742
 

Summary

Summary

Summary


Technical features WKL 900 WKL 903 WKL 1000
Select to compare:  
Working temperature range* °C -20...40 -15...40 -10...40
Temperature stability ±K 1.0 1.0 0.5
Cooling output at 20 °C kW 0.95 0.8 1.0
Pump pressure max. bar 1.0 3.2 1.0
Pump flow max. L/min 30 33 30
Cat. No. 100 V; 50 Hz/115 V; 60 Hz LWG 759 LWG 760 LWG 473 (115 V; 60 Hz)
Cat. No. 208-230 V; 60 Hz LWG 859 LWG 860
 

Summary

Summary

Summary

* Working temperature range is equal to ACC range



WK class WKL circulation chillers up to 13 kW

Technical features WKL 1200 WKL 1200 W WKL 2200 WKL 2200 W WKL 3200 WKL 3200 W
Select to compare:  
Working temperature range* °C -10...40 -10...40 -10...40 -10...40 -10...40 -10...40
Temperature stability ±K 0.5 0.5 1.0 1.0 1.0 1.0
Cooling output at 20 °C kW 1.2 1.6 2.2 2.7 3.5 4.2
Pump pressure max. bar 3.2 3.2 3.2 3.2 3.2 3.2
Pump flow max. L/min 40 40 40 40 40 40
Cat. No. 208-230 V; 60 Hz LWG 853 LWG 866 LWG 854 LWG 867
Cat. No. 208-230 V; 3/PE; 60 Hz LWG 755 LWG 768
 

Summary

Summary

Summary

Summary

Summary

Summary


Technical features WKL 4600 WKL 4600 W WKL 7000 WKL 7000 W WKL 10000 WKL 10000 W
Select to compare:  
Working temperature range* °C -10...40 -10...40 -30...40 -30...40 -30...40 -30...40
Temperature stability ±K 0.5 0.5 0.5 0.5 0.5 0.5
Cooling output at 20 °C kW 4.6 5.3 7.0 8.5 10.0 13.0
Pump pressure max. bar 3.2 3.2 6.0 6.0 6.0 6.0
Pump flow max. L/min 40 40 60 60 60 60
Cat. No. 208 V; 3/PE; 60 Hz LWG 756** LWG 757** LWG 346 LWG 348
Cat. No. 440-480 V; 3/PE; 60 Hz LWG 646 LWG 648 LWG 650 LWG 652
 

Summary

Summary

Summary

Summary

Summary

Summary

* Working temperature range is equal to ACC range
** 208-230 V; 3/PE; 60 Hz

Reinforced polymer tubing
Special polymer tubing (EPDM) for high pressures

Cat.-No.: Description Temp.-range °C Max. pressure in bar
RKJ 031 Polymer tube 1/2“ fiber-reinforced -40...100 20
RKJ 032 Polymer tube 3/4“ fiber-reinforced -40...100 20
RKJ 033 Polymer tube 1“ fiber-reinforced -40...100 20


Manifold connectors
For joining multiple external systems (for water/glycol, not suitable for silicone oil)

Cat.-No.: Description Connection Male thread Temp.-range °C
LWZ 010 Four-port manifold G 3/4“ 4 x 3/4“ -10...100
LWZ 022 Four-port manifold G 3/4“ 4 x 1/2“ -10...100
LWZ 039 Four-port manifold G 3/4“ 4 x 10 mm -10...100
LWZ 024 Four-port manifold G 1 1/4“ 4 x 3/4“ -10...100
LWZ 038 Four-port manifold M 16 x 1 4 x 10 mm -10...100
LWZ 009 Four-port manifold M 16 x 2 4 x 1/2“ -10...100


Options ex works: WK circulation chillers up to 0 °C

  Cat.-No.: WK
300
WK
500
WK
502
WK
1200
WK
1200 W*
WK
1400
WK
1400 W*
WK
2200
WK
2200 W*
WK
2400
RS 232/485 digital interface LWZ 033 -
Flow control instrument LWZ 034 - - - - - - - -
  LWZ 035 - - -
High-power pump 5.5 bar,
40 L/min. 60-Hz version
LWZ 031-2 - - - - - -
LWZ 032-2 - - - - - - - - - -
  Cat.-No.: WK
2400 W*
WK
3200
WK
3200 W*
WK
4600
WK
4600 W*
WK
7000
WK
7000 W*
WK
10000
WK
10000 W*
RS 232/485 digital interface LWZ 033
Flow control instrument LWZ 034 - - - - - - - - -
  LWZ 035
High-power pump 5.5 bar,
40 L/min. 60-Hz version
LWZ 031-2 - - - - - - - - -
LWZ 032-2 -

* W = water-cooled version



Options ex works: WK circulation chillers down to -30 °C

  Cat.-No.: WKL
230
WKL
600
WKL
603
WKL
900
WKL
903
WKL
1000
WKL
1200
WKL
1200 W*
WKL
2200
Enlarged temperature
range down to -25 °C
LWZ 030 - - - - - -
RS 232/485 digital interface LWZ 033 -
Flow control instrument LWZ 034 - v - -
LWZ 035 - - - - - -
LWZ 036 - - - - - - - - -
Low-pressure pump 1 bar,
30 L/min. 60-Hz version
LWZ 041-2 - - - - - -
High-power pump 5.5 bar,
40 L/min. 60-Hz version
LWZ 031-2 - - - - - -
LWZ 032-2 - - - - - - - - -
  Cat.-No.: WKL
2200 W*
WKL
3200
WKL
3200 W*
WKL
4600
WKL
4600 W*
WKL
7000
WKL
7000 W*
WKL
10000
WKL
10000 W*
Enlarged temperature
range down to -25 °C
LWZ 030 - - - - -
RS 232/485 digital interface LWZ 033
Flow control instrument LWZ 034 - - - - - - - - -
LWZ 035 - - - -
LWZ 036 - - - - -
Low-pressure pump 1 bar,
30 L/min. 60-Hz version
LWZ 041-2 - - - - - - - -
High-power pump 5.5 bar,
40 L/min. 60-Hz version
LWZ 031-2 - - - - - - - -
LWZ 032-2 - - - - -

* W = water-cooled version