Featured Product
New LAUDA Integral XT 280
Highly Dynamic Thermostat for External Process Control and Reactor Chemistries from
-80 °C to 200 °C.
Circulation chillers with closed cooler circuit for continuous nonstop work in research, technology and production at temperatures from -30 up to 40 °C.
LAUDA WK class circulation chillers are used where operating heat has to be discharged reliably and quickly in chemical production processes or from technical systems – in harsh constant use environments. Unlike cooling with tap water, they provide a constant temperature irrespective of the time of year and pressure fluctuations. The water saving also protects the environment and significantly reduces operating costs.
| The WK class advantages | Your benefits | |
![]() |
|
|
![]() |
|
|
![]() |
|
|
![]() |
|
|
The circulation chillers of the WK class are available with different cooling and pump configurations. The temperature range for all the units is from 0 up to 40 °C.
The LAUDA WK 300 was especially designed for simple cooling tasks down to 0 °C and is ideally suited for the use on the laboratory bench due to its compact size. The circulation chillers WK 500 and WK 502 differ in their cooling and pump output. The WK 502 was especially designed for the connection to atomic absorption spectrometers (ASS). Unlike the WK 500, it has an appropriately upgraded cooling unit and pump.
The differences between the individual units are the effective cooling and pump outputs and the dimensions. All units can be supplied with water cooling (W). This enables greater cooling performance without heating of the surrounding laboratory environment.
The different cooling capacities are critical when selecting a unit. The WK class circulation chillers from 1 kW cooling capacity upwards are also available with water-cooling (W). In the more powerful WK 7000 to WK 10000 W circulation chillers, a second pump provides the internal circulation in addition to the pump for the external circuit. Thus the cooling capacity and temperature stability do not depend on the flow characteristics in the external circuit. These units can be supplied on request with water cooling (W). For these units, the use of water/glycol mixtures as heat transfer liquid is compulsory.
The LAUDA WK circulation chillers are available with different options, e.g. RS 232/485 interface and enhanced pumping systems.
The WKL 230 circulation chiller was especially designed for simple thermostating tasks below 0 °C. Thanks to its extremely compact construction and small footprint it fits anywhere. The temperature range of the WKL 230 is from -10 °C up to 40 °C with a temperature stability of ±0.5 K. The compact circulation chillers WKL 600 to WKL 1000 have different pumps and cooling performance.
The WKL circulation chillers differ in terms of their cooling capacities and achieve temperatures of -10 °C (WKL 1200 to WKL 4600 W) or -30 °C (WKL 7000 to WKL 10000 W). All units are also available in the watercooled design (W). With these units, the use of water/glycol mixtures as the heat transfer liquid is compulsory.
Select up to 3 products to compare: Compare Products
WK class WK circulation chillers up to 600 W
| Technical features | WK 300 | WK 500 | WK 502 | |
| Select to compare: | ||||
| Working temperature range* | °C | 0...40 | 0...40 | 0...40 |
| Temperature stability | ±K | 0.5 | 0.5 | 0.5 |
| Cooling output at 20 °C | kW | 0.31 | 0.50 | 0.60 |
| Pump pressure max. | bar | 0.15 | 1.0 | 2.2 |
| Pump flow max. | L/min | 8 | 30 | 33 |
| Cat. No 100 V; 50 Hz/115 V; 60 Hz | LWM 717 | LWG 732 | – | |
| Cat. No 230 V; 60 Hz | – | LWG 232 | LWG 240 | |
* Working temperature range is equal to ACC range
WK class WK circulation chillers up to 2.8 kW
| Technical features | WK 1200 | WK 1200 W | WK 1400 | WK 1400 W | |
| Select to compare: | |||||
| Working temperature range* | °C | 0...40 | 0...40 | 0...40 | 0...40 |
| Temperature stability | ±K | 0.5 | 0.5 | 0.5 | 0.5 |
| Cooling output at 20 °C | kW | 1.2 | 1.5 | 1.4 | 1.7 |
| Pump pressure max. | bar | 3.2 | 3.2 | 1 | 1 |
| Pump flow max. | L/min | 40 | 40 | 30 | 30 |
| Cat. No. 100 V; 50 Hz/115 V; 60 Hz | LWG 733 | LWG 761 | LWG 737 | LWG 762 | |
| Technical features | WK 2200 | WK 2200 W | WK 2400 | WK 2400 W | |
| Select to compare: | |||||
| Working temperature range* | °C | 0...40 | 0...40 | 0...40 | 0...40 |
| Temperature stability | ±K | 1 | 1 | 1 | 1 |
| Cooling output at 20 °C | kW | 2.2 | 2.6 | 2.4 | 2.8 |
| Pump pressure max. | bar | 3.2 | 3.2 | 1 | 1 |
| Pump flow max. | L/min | 40 | 40 | 30 | 30 |
| Cat. No. 100 V; 50 Hz/115 V; 60 Hz | LWG 734 | LWG 763 | LWG 738 | LWG 764 | |
* Working temperature range is equal to ACC range
WK class WK circulation chillers up to 13 kW
| Technical features | WK 3200 | WK 3200 W | WK 4600 | WK 4600 W | |
| Select to compare: | |||||
| Working temperature range* | °C | 0...40 | 0...40 | 0...40 | 0...40 |
| Temperature stability | ±K | 1 | 1 | 0.5 | 0.5 |
| Cooling output at 20 °C | kW | 3.5 | 4.0 | 4.6 | 5.3 |
| Pump pressure max. | bar | 3.2 | 3.2 | 3.2 | 3.2 |
| Pump flow max. | L/min | 40 | 40 | 40 | 40 |
| Cat. No. 208-230 V; 3/PE; 60 Hz | – | LWG 765** | LWG 336 | LWG 758 | |
| Cat. No. 440-480 V; 3/PE; 60 Hz | – | – | LWG 636 | – | |
| Cat. No. 230 V; 3/PE; 60 Hz | LWG 135 | LWG 165 | – | LWG 158 | |
| Technical features | WK 7000 | WK 7000 W | WK 10000 | WK 10000 W | |
| Select to compare: | |||||
| Working temperature range* | °C | 0...40 | 0...40 | 0...40 | 0...40 |
| Temperature stability | ±K | 0.5 | 0.5 | 0.5 | 0.5 |
| Cooling output at 20 °C | kW | 7.0 | 8.5 | 10.0 | 13.0 |
| Pump pressure max. | bar | 3.2 | 3.2 | 3.2 | 3.2 |
| Pump flow max. | L/min | 40 | 40 | 40 | 40 |
| Cat. No. 208 V; 3/PE; 60 Hz | LWG 345 | LWG 347 | – | – | |
| Cat. No. 440-480 V; 3/PE; 60 Hz | LWG 645 | LWG 647 | LWG 649 | LWG 651 | |
* Working temperature range is equal to ACC range
** 208 V; 3/PE; 60 Hz
WK class WKL circulation chillers up to 1 kW
| Technical features | WKL 230 | WKL 600 | WKL 603 | |
| Select to compare: | ||||
| Working temperature range* | °C | -10...40 | -25...40 | -20...40 |
| Temperature stability | ±K | 0.5 | 1.0 | 1.0 |
| Cooling output at 20 °C | kW | 0.23 | 0.65 | 0.52 |
| Pump pressure max. | bar | 0.15 | 1.0 | 3.2 |
| Pump flow max. | L/min | 8 | 30 | 33 |
| Cat. No. 100 V; 50 Hz/115 V; 60 Hz | LWM 716 | LWG 741 | LWG 742 | |
| Technical features | WKL 900 | WKL 903 | WKL 1000 | |
| Select to compare: | ||||
| Working temperature range* | °C | -20...40 | -15...40 | -10...40 |
| Temperature stability | ±K | 1.0 | 1.0 | 0.5 |
| Cooling output at 20 °C | kW | 0.95 | 0.8 | 1.0 |
| Pump pressure max. | bar | 1.0 | 3.2 | 1.0 |
| Pump flow max. | L/min | 30 | 33 | 30 |
| Cat. No. 100 V; 50 Hz/115 V; 60 Hz | LWG 759 | LWG 760 | LWG 473 (115 V; 60 Hz) | |
| Cat. No. 208-230 V; 60 Hz | LWG 859 | LWG 860 | – | |
* Working temperature range is equal to ACC range
WK class WKL circulation chillers up to 13 kW
| Technical features | WKL 1200 | WKL 1200 W | WKL 2200 | WKL 2200 W | WKL 3200 | WKL 3200 W | |
| Select to compare: | |||||||
| Working temperature range* | °C | -10...40 | -10...40 | -10...40 | -10...40 | -10...40 | -10...40 |
| Temperature stability | ±K | 0.5 | 0.5 | 1.0 | 1.0 | 1.0 | 1.0 |
| Cooling output at 20 °C | kW | 1.2 | 1.6 | 2.2 | 2.7 | 3.5 | 4.2 |
| Pump pressure max. | bar | 3.2 | 3.2 | 3.2 | 3.2 | 3.2 | 3.2 |
| Pump flow max. | L/min | 40 | 40 | 40 | 40 | 40 | 40 |
| Cat. No. 208-230 V; 60 Hz | LWG 853 | LWG 866 | LWG 854 | LWG 867 | – | – | |
| Cat. No. 208-230 V; 3/PE; 60 Hz | – | – | – | – | LWG 755 | LWG 768 | |
| Technical features | WKL 4600 | WKL 4600 W | WKL 7000 | WKL 7000 W | WKL 10000 | WKL 10000 W | |
| Select to compare: | |||||||
| Working temperature range* | °C | -10...40 | -10...40 | -30...40 | -30...40 | -30...40 | -30...40 |
| Temperature stability | ±K | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 | 0.5 |
| Cooling output at 20 °C | kW | 4.6 | 5.3 | 7.0 | 8.5 | 10.0 | 13.0 |
| Pump pressure max. | bar | 3.2 | 3.2 | 6.0 | 6.0 | 6.0 | 6.0 |
| Pump flow max. | L/min | 40 | 40 | 60 | 60 | 60 | 60 |
| Cat. No. 208 V; 3/PE; 60 Hz | LWG 756** | LWG 757** | LWG 346 | LWG 348 | – | – | |
| Cat. No. 440-480 V; 3/PE; 60 Hz | – | – | LWG 646 | LWG 648 | LWG 650 | LWG 652 | |
* Working temperature range is equal to ACC range
** 208-230 V; 3/PE; 60 Hz
Reinforced polymer tubing
Special polymer tubing (EPDM) for high pressures
| Cat.-No.: | Description | Temp.-range °C | Max. pressure in bar |
| RKJ 031 | Polymer tube 1/2“ fiber-reinforced | -40...100 | 20 |
| RKJ 032 | Polymer tube 3/4“ fiber-reinforced | -40...100 | 20 |
| RKJ 033 | Polymer tube 1“ fiber-reinforced | -40...100 | 20 |
Manifold connectors
For joining multiple external systems (for water/glycol, not suitable for silicone oil)
| Cat.-No.: | Description | Connection | Male thread | Temp.-range °C |
| LWZ 010 | Four-port manifold | G 3/4“ | 4 x 3/4“ | -10...100 |
| LWZ 022 | Four-port manifold | G 3/4“ | 4 x 1/2“ | -10...100 |
| LWZ 039 | Four-port manifold | G 3/4“ | 4 x 10 mm | -10...100 |
| LWZ 024 | Four-port manifold | G 1 1/4“ | 4 x 3/4“ | -10...100 |
| LWZ 038 | Four-port manifold | M 16 x 1 | 4 x 10 mm | -10...100 |
| LWZ 009 | Four-port manifold | M 16 x 2 | 4 x 1/2“ | -10...100 |
Options ex works: WK circulation chillers up to 0 °C
| Cat.-No.: | WK 300 |
WK 500 |
WK 502 |
WK 1200 |
WK 1200 W* |
WK 1400 |
WK 1400 W* |
WK 2200 |
WK 2200 W* |
WK 2400 |
|
| RS 232/485 digital interface | LWZ 033 | - | |||||||||
| Flow control instrument | LWZ 034 | - | - | - | - | - | - | - | - | ||
| LWZ 035 | - | - | - | ||||||||
| High-power pump 5.5 bar, 40 L/min. 60-Hz version |
LWZ 031-2 | - | - | - | - | - | - | ||||
| LWZ 032-2 | - | - | - | - | - | - | - | - | - | - |
| Cat.-No.: | WK 2400 W* |
WK 3200 |
WK 3200 W* |
WK 4600 |
WK 4600 W* |
WK 7000 |
WK 7000 W* |
WK 10000 |
WK 10000 W* |
|
| RS 232/485 digital interface | LWZ 033 | |||||||||
| Flow control instrument | LWZ 034 | - | - | - | - | - | - | - | - | - |
| LWZ 035 | ||||||||||
| High-power pump 5.5 bar, 40 L/min. 60-Hz version |
LWZ 031-2 | - | - | - | - | - | - | - | - | - |
| LWZ 032-2 | - |
* W = water-cooled version
Options ex works: WK circulation chillers down to -30 °C
| Cat.-No.: | WKL 230 |
WKL 600 |
WKL 603 |
WKL 900 |
WKL 903 |
WKL 1000 |
WKL 1200 |
WKL 1200 W* |
WKL 2200 |
|
| Enlarged temperature range down to -25 °C |
LWZ 030 | - | - | - | - | - | - | |||
| RS 232/485 digital interface | LWZ 033 | - | ||||||||
| Flow control instrument | LWZ 034 | - | v | - | - | |||||
| LWZ 035 | - | - | - | - | - | - | ||||
| LWZ 036 | - | - | - | - | - | - | - | - | - | |
| Low-pressure pump 1 bar, 30 L/min. 60-Hz version |
LWZ 041-2 | - | - | - | - | - | - | |||
| High-power pump 5.5 bar, 40 L/min. 60-Hz version |
LWZ 031-2 | - | - | - | - | - | - | |||
| LWZ 032-2 | - | - | - | - | - | - | - | - | - |
| Cat.-No.: | WKL 2200 W* |
WKL 3200 |
WKL 3200 W* |
WKL 4600 |
WKL 4600 W* |
WKL 7000 |
WKL 7000 W* |
WKL 10000 |
WKL 10000 W* |
|
| Enlarged temperature range down to -25 °C |
LWZ 030 | - | - | - | - | - | ||||
| RS 232/485 digital interface | LWZ 033 | |||||||||
| Flow control instrument | LWZ 034 | - | - | - | - | - | - | - | - | - |
| LWZ 035 | - | - | - | - | ||||||
| LWZ 036 | - | - | - | - | - | |||||
| Low-pressure pump 1 bar, 30 L/min. 60-Hz version |
LWZ 041-2 | - | - | - | - | - | - | - | - | |
| High-power pump 5.5 bar, 40 L/min. 60-Hz version |
LWZ 031-2 | - | - | - | - | - | - | - | - | |
| LWZ 032-2 | - | - | - | - | - |
* W = water-cooled version